Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
| 10/12/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - DRYER VENTS NOT FITTING IN WALL - DRYER VENTS OVALED TOO MUCH AT CONNECTION INTO DRYER BOX - OK TO USE 3X4 DOWNSPOUT IN WALL - RELOCATE WATER LINES CONTACTING FURNACE VENTS - MUST HAVE MIN. 1" CLEARANCE - PROVIDE PG FRAMES ON ALL SIDEWALL BOXES - UNIT 5 PROVIDE SUPPLY TO BATHROOM - PROVIDE BACKING ON ALL SIDEWALL REGISTER BOXES |
|
| 09/28/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - INSULATE ALL SHEETMETAL DUCTS WITH MIN. R4.2 INSULATION WITH VAPOR BARRIER - DO NOT USE SCREWS IN DRYER VENTS - PROVIDE A PG FRAME FOR LOW COMBUSTION AIR - PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES AROUND B VENTS - SOME DRYER VENTS INSTALLED BACKWARDS - PROVIDE PLATE STRAPS AT DRYER VENTS WHERE NEEDED - PROVIDE INSULATED COPPER CONDENSATE DRAINS AS PER PLANS - OK TO USE ONE OPENING METHOD OF COMBUSTION AIR |