Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 03/13/2008 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
| 03/12/2008 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE APPROVED PLANS ON SITE 2. HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN EQUIPMENT |
|
| 02/22/2008 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO SPLICES IN WALL 2. CABLE JACKET TO BE MIN. 1/4" IN PANEL AND MAIN BONDING JUMPER 3. BONDING JUMPERS NOT SIZED PROPERLY 4. GROUND RODS TO BE MIN. 6' APART 5. BOND ALL GAS PIPING TO APPROPRIATE SERVICES 6. HAVE APPROVED PLANS ON SITE |