Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/07/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC SUPPORTS TO BE WITHIN 12" OF TERMINATION AND AT 6' INTERVALS PER NEC. SUPPORTS TO BE INDEPENDENT OF GRID SUPPORT. 2. DATA/COMM CABLING MUST BE SUPPORTED PER NEC 725-800 INDEPENDENT OF GRID SUPPORT OR OTHER TRADE SUPPORT OR SYSTEMS. |
|
| 12/04/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SEISMICS & SCREW TO GRID 2X4 LAYIN FIXTURES. 2. SUPPORT MC PER CODE |