Permit: T06CM05293

Parcel: 134050770

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/17/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/16/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C UNIT SPECIFICATIONS DO NOT ALLOW AN EXTERIOR TRAP ON CONDENSATE LINE OF THIS UNIT
2) CAP OFF OPEN AT VENT IN PVC LINE