Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED LETTER FROM ENGINEER TO BE ADDED TO PLANS FOR STANDBY GENERATOR CONNECTED TO EM & NL LIGHTS 2. SIGNAGE NEEDED PER 700.8 3. FINISH #3 PREVIOUS INSPECTION |
|
| 12/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EXIT SIGN NOT WORKING (SE CORNER) 2. LABEL BREAKERS AS TO WHERE THEY CONTROL 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING AT NEW REPECTACLES/DEVICES 314.20 4. NEED TO CHECK LIGHTING AS PER 700.12 - AREA SERVED 5. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN SERVICE EQUIPMENT. |