Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING NOT PER PLAN/MISSING 2 2. PANEL DIRECTORY NOT CORRECTLY IDENTIFED - NEC 408.4 3. BREAKERS USED AS LIGHTING SWITCH NEED "SWD" RATED NEC 240.83 4. CIRCUITRY FOR LIGHTING AND RECEPTACLES NOT PER PLAN. 5. SECURE TRANSFORMER TO FLOOR AND PROVIDE GROUNDING ELECTRODE FOR IT -- NEC 110.13, NEC 250.30 6. BOXES TO BE FLUSH TO SURFACE FOR RECEPTACLES OR USE EXTENDER -- NEC 314.20 7. SECURE LIGHTING TRACKS AT MAX 4' INTERVALS AND MAKE SURE MAXIMUM CONNECTED LOAD IS NOT EXCEEDED NEC 410.104, 410.101 A, B |