Permit: T06CM05286

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05286

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING NOT PER PLAN/MISSING 2
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFED - NEC 408.4
3. BREAKERS USED AS LIGHTING SWITCH NEED "SWD" RATED NEC 240.83
4. CIRCUITRY FOR LIGHTING AND RECEPTACLES NOT PER PLAN.
5. SECURE TRANSFORMER TO FLOOR AND PROVIDE GROUNDING ELECTRODE FOR IT -- NEC 110.13, NEC 250.30
6. BOXES TO BE FLUSH TO SURFACE FOR RECEPTACLES OR USE EXTENDER -- NEC 314.20
7. SECURE LIGHTING TRACKS AT MAX 4' INTERVALS AND MAKE SURE MAXIMUM CONNECTED LOAD IS NOT EXCEEDED
NEC 410.104, 410.101 A, B