Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - USE OUTDOOR FITTINGS ONLY ON ELEC. CONDUIT. - PROVIDE A ROOF JACK AT ROOF PENETRATIONS. - SEAL ALL SCREW HOLES & SPOT WELD HOLES IN DUCT ON ROOF. - PROPERLY SUPPORT DUCT ON ROOF. - PROVIDE THE PROPER VENT ASSEMBLY FOR FURNACE. - MUST USE 3/4" DRAIN PIPE ON CONDENSATE DRAIN. - GLUE FITTINGS & TERMINATE WITHIN 6" OF THE GROUND & DIVERT THE WATER AWAY FROM THE HOUSE. - BLOCK & CLAMP EVERY 4' & PAINT W/LATEX PAINT. - DO NOT MOUNT ELEC. DISCONNECT ON A REMOVABLE PANEL. - USE DUCT SEALER TO SEAL DUCTS NOT TAPE. - LOW VOLTAGE WIRE MUST BE IN CONDUIT. - EXPOSED DUCT ON ROOF REQUIRES R-8 DUCT LINE (2") - PRESSURE TEST ON GAS PIPING - PROVIDE 15 LB. GAUGE - USE ONLY REDWOOD OR PRESSURE TREATED WOOD ON ROOF. |