Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/21/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REQUIRED TO HAVE PLAN, PERMIT AND PREVIOUS INSPECTION HISTORY ON SITE AT ALL TIMES!!! 2. FINISH INSULATING H.C LAVATORY |
|
| 04/06/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEE NOT #8 FROM INSPECTION DONE ON 3/30/07-THIS INCLUDES LAV CARRIER |
|
| 03/30/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. 4.4 PSI TEST 2. SEDIMENT TRAP MUST BE 4" ABV ROOF, INSTALL AT FURN CONNECTION. 3. HAVE FURNACE INSPECTED 4. CONDENSATE NOT COMPLETE. 5. UPC SEC 313.2 PROHIBITS PIPING FROM BEING EMBEDDED IN CONCRETE. 6. UPC SEC IS #5 PG 320 REQUIRES CLOSET FLANGES TO BE FASTENED TO THE FLOOR. 7. COMPLETE VACUUM BREAKER INSTALLATION AT LAUNDRY TUB. 8. FIXTURES NOT PER PLAN SPECS. 9. CAULK LAVITORY. |
|
| 03/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 15 PSI ON GAS PIPING TAR BLOCKS TO ROOF INSTALL SEDIMENT TRAP & CHECK FLEX RATING PROVIDE PLANS POST SUITE NUMBER IDENTIFY PIPING AT GAS METER REMOVE TOILET FOR FLANGE INSPECTION NOTE WC HANDLE NOT ACCESSIBLE MAKE ACCESS PANEL FOR CO ACCESSIBLE MAKE CLEANOUTS WATER & GAS TIGHT USE PROPER CLEAN OUT PLUG AT LAUNDRY TUB HOSE THREADS REQUIRE A VACUUM BREAKER |