Permit: T06CM05278

Parcel: 12218431A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/24/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
05/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. REQUIRED TO HAVE PLAN, PERMIT AND PREVIOUS INSPECTION HISTORY ON SITE AT ALL TIMES!!!
2. FINISH INSULATING H.C LAVATORY
04/06/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOT #8 FROM INSPECTION DONE ON 3/30/07-THIS INCLUDES LAV CARRIER
03/30/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. 4.4 PSI TEST
2. SEDIMENT TRAP MUST BE 4" ABV ROOF, INSTALL AT FURN CONNECTION.
3. HAVE FURNACE INSPECTED
4. CONDENSATE NOT COMPLETE.
5. UPC SEC 313.2 PROHIBITS PIPING FROM BEING EMBEDDED IN CONCRETE.
6. UPC SEC IS #5 PG 320 REQUIRES CLOSET FLANGES TO BE FASTENED TO THE FLOOR.
7. COMPLETE VACUUM BREAKER INSTALLATION AT LAUNDRY TUB.
8. FIXTURES NOT PER PLAN SPECS.
9. CAULK LAVITORY.
03/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
15 PSI ON GAS PIPING
TAR BLOCKS TO ROOF
INSTALL SEDIMENT TRAP & CHECK FLEX RATING
PROVIDE PLANS
POST SUITE NUMBER
IDENTIFY PIPING AT GAS METER
REMOVE TOILET FOR FLANGE INSPECTION
NOTE WC HANDLE NOT ACCESSIBLE
MAKE ACCESS PANEL FOR CO ACCESSIBLE
MAKE CLEANOUTS WATER & GAS TIGHT
USE PROPER CLEAN OUT PLUG AT LAUNDRY TUB
HOSE THREADS REQUIRE A VACUUM BREAKER