Permit: T06CM05278

Parcel: 12218431A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/06/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
YOU MAY COVER WALLS BUT YOU WILL NEED A 12 X 12 ACCESS PANEL TO ACCESS CLEANOUT UNDER LAV THAT IS 6" BACK FROM FINISHED WALL.
12/29/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE REVISION FOR CHANGES AT P-3 AND FOR GAS PIPING DELETION AND RED LINE PLANS. CLEANOUT EXTENSIONS AND HORIZONTAL CHANGES OF DIRECTION SHALL BE MADE WITH WYE PATERSON FITTINGS. USE COMBUSTION FITTINGS AND SWEEPS AT ALL CLEANOUTS AND TRAP ARM OR POSITION CLEANOUT OPENINGS SO THAT DIRECT ACCESS CAN BE OBTAINED. WATER TEST THRU ROOF. SUPPORT HORIZONTAL VENT ABOVE CEILING. SECURE CLOSET FLANGE WITH FASTENERS. COMPLETE WATER PIPING AT MOP SINK