Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ROOF: MAINTAIN WORKING CLEARANCE IN FRONT OF A/C DISCONNECT-GAS LINE 2) OK ALL OTHER ITEMS |
|
| 03/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL A DISCONNECTING MEANS FOR WATER HEATER NEC 422.31B 2. HAVE SEVERAL "DEAD" RECEPTACLES -- WEST SIDE 3. HAVE SEVERAL LOOSE RECEPTACLES - NEC 406.4 INSTALL ALL COVER PLATES 4. PROVIDE LADDER FOR ROOF ACCESS |
|
| 03/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 ALSO, OPENING TO BE 1/8" OR LESS 314.21 2. INSTALL DEVICES INTO BOXES & INSTALL PLATES 3. INSTALL DISCONNECT FOR INSTA-HOT 4. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 5. TIGHTEN LOOSE CONDUCTOR TERMINATIONS 6. LABEL CIRCUIT DIRECTORY 7. INSTALL REJECTION PINS & FUSES 8. NEED ACCESS TO SERVICE GUTTER 9. INSTALL SERVICE CONDUCTORS |