Permit: T06CM05278

Parcel: 12218431A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ROOF: MAINTAIN WORKING CLEARANCE IN FRONT OF A/C DISCONNECT-GAS LINE
2) OK ALL OTHER ITEMS
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL A DISCONNECTING MEANS FOR WATER HEATER
NEC 422.31B
2. HAVE SEVERAL "DEAD" RECEPTACLES -- WEST SIDE
3. HAVE SEVERAL LOOSE RECEPTACLES - NEC 406.4 INSTALL ALL COVER PLATES
4. PROVIDE LADDER FOR ROOF ACCESS
03/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 ALSO, OPENING TO BE 1/8" OR LESS 314.21
2. INSTALL DEVICES INTO BOXES & INSTALL PLATES
3. INSTALL DISCONNECT FOR INSTA-HOT
4. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL
5. TIGHTEN LOOSE CONDUCTOR TERMINATIONS
6. LABEL CIRCUIT DIRECTORY
7. INSTALL REJECTION PINS & FUSES
8. NEED ACCESS TO SERVICE GUTTER
9. INSTALL SERVICE CONDUCTORS