Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILINGS |
|
| 08/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT USE DRAIN PIPE AS ELECTRICAL RACEWAY FOR TELEPHONE DATA CABLE. NEED TO INSTALL RECOGNIZED WIRING METHOD OF CHAPTER 3 OF NEC 2) CANNOT USE EMT FOR SUPPORT OF LOW VOLTAGE WIRING. CABLE TV, THERMOSTAT, TELEPHONE, ETC... |
|
| 07/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CEILINGS AT ENTRY & DRIVE THRU 2. INSTALL ACCESS OPENINGS AS DISCUSSED 3. CANNOT USE LIGHT JUNCTION BOXES AS RACEWAY. MAKE CORRECTION AS DISCUSSED |
|
| 07/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |