Permit: T06CM05276

Parcel: 13101071E


Addresses:

2222 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/31/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILINGS
08/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT USE DRAIN PIPE AS ELECTRICAL RACEWAY FOR TELEPHONE DATA CABLE. NEED TO INSTALL RECOGNIZED WIRING METHOD OF CHAPTER 3 OF NEC
2) CANNOT USE EMT FOR SUPPORT OF LOW VOLTAGE WIRING. CABLE TV, THERMOSTAT, TELEPHONE, ETC...
07/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILINGS AT ENTRY & DRIVE THRU
2. INSTALL ACCESS OPENINGS AS DISCUSSED
3. CANNOT USE LIGHT JUNCTION BOXES AS RACEWAY. MAKE CORRECTION AS DISCUSSED
07/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS