Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS 7 & 8 2) NO INTERIOR OR ROOF INSPECTIONS MADE AT THIS TIME |
|
| 02/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PREVENT OBSTRUCTABLE CURRENT 250.6 2) HIGH LEG PAST CT CAN TO BE AS PER 408.3 (E) 3) INSTALL REJECTION PINS 4) USE LUGS LISTED FOR CONDUCTOR SIZES 5) NEUTRALS FULLY EXPOSED WHITE 200.7 6) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 7) CHECK DERATING PER 310.15 8) PLEASE REVISE PLANS TO REFLECT WORK INSTALLED |