Permit: T06CM05271

Parcel: 12613018A


Addresses:

4530 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05271

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. LETTER ON APPROVED USE OF PVC & FLEX OVER 3' BY EE ON FINAL.
2. SEE DERATE NOTE ON LAST INSPECTION
12/20/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/20/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL METAL BOXES TO BE GROUNDED
2. HOLE IN PNL TO BE SEALED
3. FINISH ALL MC CABLES INTO PANELS
4. UNFINISHED BOX NEXT TO SMALL PNL
5. PLASTER RING IN BATHROOM SW
TOO MANY LOOSE ENDS - REVIEW ALL INTERMEDIATE WORK PRIOR TO CALL FOR INSPECTION.
12/20/2006 ELECTRIC - INTERMEDIATE Denied 1. SUPPORT VDV CABELING IN WALLS AND ABOVE CEILINGS
725.3&6, 800.3 & 6
2. PROTECT FLEX CONDUITS TO SHALLOW STUDS ALSO, M/C AT STUDS.
3. SUPPORT M/C CABLE WITHIN 12" OF BOXES AND 6' ABOVE HARD LID.
4. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF FLEX & PVC CONDUIT -- PLANS DO NOT ALLOW #4 C & D
5. SUPPORT CONDUIT COMING OUT OF GROUND
6. PROTECT PVC CONDUITS AT BASE PLATES
7. SUPPORT PVC CONDUITS BELOW PANEL
8. PREVENT DIELECTRIC CONTACT

*NOTE TO DERATE CONDUCTOR PER 310.15
*IF USED LB COVER TO BE ACCESSIBLE
12/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*