Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05271
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. LETTER ON APPROVED USE OF PVC & FLEX OVER 3' BY EE ON FINAL. 2. SEE DERATE NOTE ON LAST INSPECTION |
|
12/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/20/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL METAL BOXES TO BE GROUNDED 2. HOLE IN PNL TO BE SEALED 3. FINISH ALL MC CABLES INTO PANELS 4. UNFINISHED BOX NEXT TO SMALL PNL 5. PLASTER RING IN BATHROOM SW TOO MANY LOOSE ENDS - REVIEW ALL INTERMEDIATE WORK PRIOR TO CALL FOR INSPECTION. |
|
12/20/2006 | ELECTRIC - INTERMEDIATE | Denied | 1. SUPPORT VDV CABELING IN WALLS AND ABOVE CEILINGS 725.3&6, 800.3 & 6 2. PROTECT FLEX CONDUITS TO SHALLOW STUDS ALSO, M/C AT STUDS. 3. SUPPORT M/C CABLE WITHIN 12" OF BOXES AND 6' ABOVE HARD LID. 4. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF FLEX & PVC CONDUIT -- PLANS DO NOT ALLOW #4 C & D 5. SUPPORT CONDUIT COMING OUT OF GROUND 6. PROTECT PVC CONDUITS AT BASE PLATES 7. SUPPORT PVC CONDUITS BELOW PANEL 8. PREVENT DIELECTRIC CONTACT *NOTE TO DERATE CONDUCTOR PER 310.15 *IF USED LB COVER TO BE ACCESSIBLE |
|
12/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |