Permit: T06CM05245

Parcel: 10715058A


Addresses:

2726 N GERONIMO AV

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
11/29/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
10/13/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PER PLOT PLAN PORCH TO CLOSE TO PROPERTY LINE. MUST CUT EXISTING CONCRETE, EXCAVATE DIRT, INSTALL REBAR AND RECALL FOR INSPECTION (BE SURE SETBACK DIMENSIONS ARE PER APPROVED PLOT PLAN) FOOTING TO BE 24" X 24" X 12" DEEP COMPLETE THIS AND RECALL
2) REFRAME AFTER MOVING FOUNDATION