Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/15/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) LETTER FROM ENGINEER APPROVES CHANGE IN TJ1 110 IN LIEU OF TJ1 ? ? BUT USED 14" ON CENTER FOR CALC'S. NEED LETTER OK-TJ1 110 SPACED AT 16" ON CENTER, AS USED |
|
| 06/13/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED ENGINEER APPROVAL OF USE OF TJ110 INSTEAD OF TJ150 ? 2) PROTECTION PLATES NEEDED AT DOWNSTAIRS BATHROOM AND STRAPS 3) GAVE PERMISSION TO INSULATE EXTERIOR WALLS AND CEILING AT OWN RISK-PENDING VERIFICATION OF TRUSS LOAD ? BETWEEN TJ110 AND TJ150 |
|
| 06/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIREBLOCKING BALLON FRAME AT STAIRWAY 2) FIREBLOCKING AT STRINGER STAIRWAY 3) NOT ? AT PATIO ROOF 4) HOLE IN EAST SIDE OF HOME 5) MISSING PROTECTION PLATES THROUGHOUT PLUMBING 6) NEED TO BLOCK MECHANICAL DUCT 3 SIDES 7) GAS BOND NOT CONNECTED 8) GROUT TUBS AND SHOWERS 9) CHASE AT GAME NEEDS FIRESTOP 10) QUESTIONS ON TJI USED-DRAWINGS CALLS FOR 150-BUILDER USED 110 |
|
| 04/27/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) INCOMPLETE |