Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* ON FINAL PROVIDE FUSES IN DISCONNECTS, CAP UNUSED CONDENSATE OUTLETS, CONNECT ALL ELEC. DEVICES, PROVIDE TRAPS ON CONDENSATE DRAINS. SECURE DISCHARGE COPPER LINE FOR UNIT #3 COPPER CANNOT CONTACT STEEL. FINISH INSULATING LINE SETS. OK FOR PARTIAL CEILING TILES. |
|
| 02/15/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED REFER LINES PRESSURE OK TO PROCEED |