Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 2002 NEC 408.3 E PHASE ARRANGEMENT CALLS FOR HIGH LEG TO BE ON B PHASE ON PANEL BOARDS. |
|
| 02/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AFTER HRS 1. INSTALL SIGN CIRCUIT 2. PROVIDE AS BUILT FOR ELECTRICAL PLAN CHANGES ON ONE LINE DIAGRAM 3. RE IDENTIFY ALSO HIGH LEG CIRCUITS AS ORANGE 4. PERMANENTLY ID MAIN PNL O/S AS 120/240 HIGH LEG SYSTEM FOR FINAL |
|
| 02/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |