Permit: T06CM05240

Parcel: 12510004B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05240

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/15/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. ADD 02090 TO PERMIT
2. CANNOT TRIM CONDUCTORS
3. INSTALL ALL STRANDS UNDER TERMINAL LUGS
4. TIGHTEN LOOSE FITTINGS
5. SERVICE RECEPTACLE NOT WORKING

STORE:
1. TIME CLOCK - INSTALL CONDUCTORS AS PER MANUFACTURES REQUIREMENTS
2. LABEL ELECTRICAL EQUIPMENT
3. LABEL CIRCUIT DIRECTORY AS PER 404.8 -- NO ABBREVIATIONS.
4. INSTALL ALL STRANDS UNDER TERMINAL LUGS
5. CORDS NOT ALLOWED PERMANENT WIRING 400.7 & 8
INSTA-HOT
6. PLEASE PROVIDE ACCESS TO INSPECT TAP CONDUCTORS AND JUNCTION BOXES.
05/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/10/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROOFTOP UNITS
1. EQUIPMENT GROUND NOT PROPERLY IDENTIFIED
2. NEED BUSHING #4 & LARGER CONDUCTOR
3. GROUND DISCONNECTS, INSTALL FUSES, STRAP FLEX
OPEN NEUTRAL ON SERVICE RECEPTACLE
4. EMERGENCY LIGHTING TO BE PER NEC 700.12 (FED FROM LIGHTING IN AREA)
5. INSTALL HOT NOT PROPERLY WIRED -- NEC 422
05/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*.
1) INSTALL UNIT # ON UNIT
2) INSTALL C LEG FUSE AT MAIN DISCONNECT
04/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK TO INSTALL TILES - CHECK EQUIPMENT GROUND I.D
NEC 250.119
11/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER
NOTE: CHECK SHELL PLAN TO MAKE SURE IT DOES NOT SHOW ANY ADDITIONAL WALL ELECTRICAL.