Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH ITEMS 1 & 2 OF PREVIOUS INSPECTION 2. DENTAL EQUIPMENT TO BE LISTED & LABELED 3. MAINTAIN WORKING CLEARANCE IN FRONT OF PANELS - 110.26 4. PLEASE LABEL PANELS ON OUTSIDE OF COVER 5. PANEL SCHEDULE TO BE AS PER 408.4 -- NO ABBREVIATIONS |
|
| 01/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP C OF O PHASE 1 1. FINISH PREVIOUS ITEMS |
|
| 01/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 2. REMOVE EXCESS FOREIGN MATERIAL FROM DEVICES 110.12 3. CORRECTLY LABEL CIRCUIT DIRECTORY AS TO WHAT AND WHERE, NO ABBREVIATIONS. 4. GROUND DEVICES 5. LIGHTING NOT AS PER PLANS 6. FINISH PREVIOUS ITEMS #1,2,3 |