Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/20/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. DENTAL LIGHTS TO BE AS PER 517.13 2. NEED BOXES FOR DENTAL LIGHTS 3. PLEASE VERIFY ALL RECEPTACLES IN PATIENT CARE AREAS MEET THE REQUIREMENTS OF 517.13 OK TO TILE EXCEPT AS NOTED |
|
| 01/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PHASE 1 |
|
| 01/05/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/03/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/06/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. CONDUIT AND MC TO BE ATTACHED AT BOTH ENDS - 300.11 2. VDV CABELING TO BE INDEPENDENTLY SUPPORTED - 300.3 3. FIXTURES TO BE ATTACHED TO GRID 410.16 4. SUPPORT WIRES NEEDED FOR CANS * BOXES MORE THAN 1/4" FROM BOX TO SURFACE MAY NEED APPROVED EXTENDER RINGS. 314.20 |