Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES PROVIDE AUDIBLE & VISIBLE ALARM FOR DUCT SMOKE DETECTOR. WILL CHECK ON FINAL OK FOR CEILING TILES. |
|
| 03/14/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE MIN R5 DUCT INSULATION AS PER PLANS & I.F.C.C PROVIDE CONDENSATE DRAIN PROVIDE DUCT SMOKE DETECTOR PROVIDE PERMITS FOR 2 NEW A/C UNITS ON ROOF |