Permit: T06CM05227

Parcel: 13612833A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06CM05227

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/02/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
FROM METER LOCATION TO STUB OUT AT FRYER OK
1. SHALL SEAL FLASHING ON ROOF
2. SHALL RETEST AFTER ANSUL VALVE INSTALL WITH GAS SHUT OFF VALVE IN PLACE WITH QUICK DISCONNECT & SAFETY CABLES.
03/22/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
25 PSI TEST FROM METER PER PLAN TO AAV AND STUB OVER ON ROOF TO DROP LOCATION ON ROOF FOR NEW FRYER OK

SHALL RETEST FOR PIPING COMPLETION THRU ANSUL VALVE WITH SHUT OFF VALVES TO APPLIANCES
03/14/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS
2. PROVIDE CORRECT 2-HOLE STRAPS FOR PIPING ON ROOF WITH MASTIC UNDER BLOCKS.