Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM05227

Parcel: 13612833A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05227

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK WALLS IN EXISTING PIZZA HUT SPACE
2. RECEIVED LETTER FOR USE OF CUTLER HAMMER BKRS.
04/06/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) NO ONE ON SITE TO DIRECT TO INSPECTION AREA
2) CALLED AND LEFT MESSAGE-NO ONE CALLED BACK
04/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE LISTING ON CHALLENGE PANEL THAT IT IS OK
TO INSTALL CUTLER HAMMER BREAKERS.
03/29/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 4" SQUARE BOX ABOVE ALARM PANEL NEEDS OPEN KNOCKOUTS SEALED PER NEC 110.112 WILL CHECK AT FINAL
2. OK TO CLOSE COOLING
03/26/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN JUNCTION BOX ABOVE ALARM PANEL
2) JUNCTION BOX ABOVE ALARM PANEL IS OVERFILLED NEC TABLE 314.16
3) SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES ABOVE CEILING NEC 110.12
4) INSTALL TIE WIRES TO EXIT LIGHTS
5) INSTALL CEILING SUPPORT WIRES FOR MC CABLE PER NEC 300.11
03/22/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. ALL LIGHTING TO HAVE SEISMIC WIRES 2X4 ONE ON EACH END & CLIPS RECESSED LIGHTS 1 ONLY
2. FOR POWER TRIM OUT PNL & HAVE COVER ON