Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05225
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PERMANENT PANEL SCHEDULE & LABEL OUTSIDE OF PANEL AS "PANEL B" 2. DISCONNECT TO WATER HEATER IMPROPERLY SET TO WALL CLOSE OF OPENINGS ON SIDES. 3. ALL DATA & COMM TO BE COMPLETED 4. MARK AC DISCON ON ROOF WITH PNL & CIR #'S 5. TAPE LOAD SIDE AC MID PHASE WITH RED NOT YELLOW YELLOW 277/480 U COLOR |