Permit: T06CM05225

Parcel: 12108303A


Addresses:

6236 E PIMA ST #190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PERMANENT PANEL SCHEDULE & LABEL OUTSIDE OF PANEL AS "PANEL B"
2. DISCONNECT TO WATER HEATER IMPROPERLY SET TO WALL CLOSE OF OPENINGS ON SIDES.
3. ALL DATA & COMM TO BE COMPLETED
4. MARK AC DISCON ON ROOF WITH PNL & CIR #'S
5. TAPE LOAD SIDE AC MID PHASE WITH RED NOT YELLOW
YELLOW 277/480 U COLOR