Permit: T06CM05224

Parcel: 136406780


Addresses:

9630 E 22ND ST #110


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM05224

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2007 MECHANICAL - FINAL Approved PER INSP CARD
05/09/2007 MECHANICAL - FINAL Partial Approval AIR BALANCE OK
SMOKE DETECTOR NOT WORKING
05/08/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DUCT SMOKE DETECTORS NOT WORKING
PROVIDE A SMOKE TEST FOR FINAL INSPECTION
PROVIDE AIR BALANCE REPORT
PRE-TEST DUCT SMOKE DETECTORS WITH SMOKE PRIOR TO SCHEDULING NEXT INSPECTION
05/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FINISH CONNECTING DUCT SMOKE DETECTORS & ALARMS
PROVIDE AIR BALANCE REPORT
OK TO FILE FOR TEMP C OF O
05/02/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PERMANENTLY ID UNIT ON ROOF
EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF
REMOVE SCREEN FROM DRYER VENT
PROVIDE AIR BALANCE REPORT