Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05224
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2007 | MECHANICAL - FINAL | Approved | PER INSP CARD | |
| 05/09/2007 | MECHANICAL - FINAL | Partial Approval | AIR BALANCE OK SMOKE DETECTOR NOT WORKING |
|
| 05/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DUCT SMOKE DETECTORS NOT WORKING PROVIDE A SMOKE TEST FOR FINAL INSPECTION PROVIDE AIR BALANCE REPORT PRE-TEST DUCT SMOKE DETECTORS WITH SMOKE PRIOR TO SCHEDULING NEXT INSPECTION |
|
| 05/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FINISH CONNECTING DUCT SMOKE DETECTORS & ALARMS PROVIDE AIR BALANCE REPORT OK TO FILE FOR TEMP C OF O |
|
| 05/02/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PERMANENTLY ID UNIT ON ROOF EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF REMOVE SCREEN FROM DRYER VENT PROVIDE AIR BALANCE REPORT |