Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05224
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEM #4 & #8 FROM INSPECTION ON 5/2/07 2. COMPLETE ITEM #1 FROM INSPECTION ON 4/23/07 OK FOR TEMP C OF O |
|
| 05/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL EXTENSIONS ON BOXES FOR RECEPTACLES IN WOOD PANELS. 2. INSTALL EXTENSION ON GFI RECEPT WOMENS ROOM 3. INSTALL DISCONNECT ON FAN COILS IN WALK IN COOLERS TO BE WITHIN SIGHT OF 4. SEAL ALL RACEWAYS INTO WALK IN COOLERS 5. EM LIGHT MENS ROOM NOT WORKING 6. EM/NL AT BACK AREA APPEARS TO BE ON SWITCH 6G NEEDS CONSTANT POWER 7. INSTALL LABEL ON PANEL B 8. INDICATE ACCESSORIES AT ROOFTOP UNIT |