Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05224

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/26/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
DOORS LOCKED
NO ACCESS
04/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. NEED TO MONITOR DUCT SMOKE DETECTORS. WILL CHECK AT FINAL.
2. OK CEILINGS
3. IDENTIFY CONDUCTORS AT PANELS PROPERLY
4. INSTALL LABEL AT BREAKER FOR PANEL TO SPACE

OK TO CLEAR COMMERCIAL TEC
04/19/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRE OVERFILL ON JUNCTION BOXES -- NEC 314.16
2. PROVIDE INFORMATION OF LOW VOLTAGE LIGHTING SYSTEM NEEDS TO BE LISTED SYSTEM -- NEC 411.3 & 110.3
3. CLASS 1 CIRCUITS (LOW VOLTAGE LIGHTING) CANNOT OCCUPY SAME RACEWAY AS POWER CONDUCTORS UNLESS EQUIPMENT IS FUNCTIONALLY ASSOCIATED. NEC 725.26
4. HOW ARE SMOKE DETECTORS FOR ROOFTOP UNIT BEING MONITORED.
5. OPEN JUNCTION BOXES IN CEILING AT BACK OF STORE
6. CANNOT VERIFY GROUND CONNECTION ON SAME JUNCTION BOXES IN CEILING.
04/06/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/05/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*