Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM05224
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/26/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* DOORS LOCKED NO ACCESS |
|
| 04/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. NEED TO MONITOR DUCT SMOKE DETECTORS. WILL CHECK AT FINAL. 2. OK CEILINGS 3. IDENTIFY CONDUCTORS AT PANELS PROPERLY 4. INSTALL LABEL AT BREAKER FOR PANEL TO SPACE OK TO CLEAR COMMERCIAL TEC |
|
| 04/19/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRE OVERFILL ON JUNCTION BOXES -- NEC 314.16 2. PROVIDE INFORMATION OF LOW VOLTAGE LIGHTING SYSTEM NEEDS TO BE LISTED SYSTEM -- NEC 411.3 & 110.3 3. CLASS 1 CIRCUITS (LOW VOLTAGE LIGHTING) CANNOT OCCUPY SAME RACEWAY AS POWER CONDUCTORS UNLESS EQUIPMENT IS FUNCTIONALLY ASSOCIATED. NEC 725.26 4. HOW ARE SMOKE DETECTORS FOR ROOFTOP UNIT BEING MONITORED. 5. OPEN JUNCTION BOXES IN CEILING AT BACK OF STORE 6. CANNOT VERIFY GROUND CONNECTION ON SAME JUNCTION BOXES IN CEILING. |
|
| 04/06/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |