Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/11/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND ALL METAL BOXES WITH EQUIPMENT GROUND.
2. 2/0 FEEDER IS OVERFUSED -- NEC 310
3. EMERGENCY LIGHTING NEEDS WIRED TO CKT THAT FEEDS THAT AREA -- NEC 700.12 (E)
4. HAVE UNDERSIZED EQUIPMENT GROUND TO ROOFTOP UNIT NEC 250.122
5. ROOFTOP UNIT HAS NO ELECTRICAL LABEL, PROVIDE SERVICE RECEPTACLE, DISCONNECT NEEDS 36" FRONT CLEARANCE -- NEC 110
6. CORRECTLY IDENTIFY PANEL DIRECTORY -- NEC 408.4