Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND ALL METAL BOXES WITH EQUIPMENT GROUND. 2. 2/0 FEEDER IS OVERFUSED -- NEC 310 3. EMERGENCY LIGHTING NEEDS WIRED TO CKT THAT FEEDS THAT AREA -- NEC 700.12 (E) 4. HAVE UNDERSIZED EQUIPMENT GROUND TO ROOFTOP UNIT NEC 250.122 5. ROOFTOP UNIT HAS NO ELECTRICAL LABEL, PROVIDE SERVICE RECEPTACLE, DISCONNECT NEEDS 36" FRONT CLEARANCE -- NEC 110 6. CORRECTLY IDENTIFY PANEL DIRECTORY -- NEC 408.4 |