Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05219
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ALL WALLS |
|
04/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL METAL FLEX IN CONTINUOUS PIECE 2. 30 AMP CIRCUITS REQUIRE #10 GROUND TO BOX 3. OK TO SHEETROCK ALL WALLS EXCEPT UTILITY ROOM WALL 4. OK TO SHEETROCK RESTROOM CEILING 5. RECALL FOR INSPECTION ON UTILITY ROOM WALL |