Permit: T06CM05219

Parcel: 136406740


Addresses:

9660 E 22ND ST #140


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05219

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ALL WALLS
04/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL METAL FLEX IN CONTINUOUS PIECE
2. 30 AMP CIRCUITS REQUIRE #10 GROUND TO BOX
3. OK TO SHEETROCK ALL WALLS EXCEPT UTILITY ROOM WALL
4. OK TO SHEETROCK RESTROOM CEILING
5. RECALL FOR INSPECTION ON UTILITY ROOM WALL