Permit: T06CM05217

Parcel: 12108281A


Addresses:

6246 E PIMA ST #180


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM05217

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2007 FRAMING Approved IVRS - Inspection :*
OK TO SHEETROCK
12/28/2006 FRAMING Partial Approval IVRS - Inspection :*
1) TREATMENT ROOMS #1 THRU #6; INTERIOR WALLS CALL FOR 4B TYPE WALLS AS PER PARTITION SCHEDULE IN PLANS; PAGE A1 1 5/8 METAL STUDS WERE USED-PLANS CALL FOR 3 5/8 METAL STUDS. PLEASE PROVIDE RFI APPROVING THE USE OF 1 5/8 STUDS IN THE SUBJECT AREAS
2) OK TO SHEETROCK PROGRESS (ONE SIDE) AREAS EXCEPT FOR THE ABOVE MENTIONED AREAS