Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH ELECTRIC |
|
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION 1. BATH LIGHT J-BOX IS OVERFILLED -- NEC 314.16 (CHECK OTHERS) 2. INSTALL NAIL PLATES AS NEEDED -- NEC 300.4 A 1 3. PROVIDE PROPER GROUNDING MEANS FOR ALL METAL BOXES -- NEC 250.110 4. IN ROOF J-BOX A. NEUTRAL NOT ALLOWED TO GROUND ENCLOSURE PROVIDE A PROPERLY SIZED EQUIPMENT GROUND - NEC 250.24 A5 B. SELF TAP SCREW NOT ALLOWED FOR GROUNDING PROVIDE PROPER EQUIPMENT GROUND TERMINATION -- NEC 250.8 C. PROVIDE A BUSHING FOR CONDUCTOR PROTECTION WHERE NEC 300.4 THEY ENTER RACEWAY -- NEC 300.4 5. PROVIDE HALLWAY RECEPTACLE -- NEC 210.52 A 6. BATH RECEPTACLES TO BE DEDICATED -- NEC 210.11 C3 |