Permit: T06CM05199

Parcel: 110053710

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/09/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK ROUGH ELECTRIC
11/07/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION
1. BATH LIGHT J-BOX IS OVERFILLED --
NEC 314.16 (CHECK OTHERS)
2. INSTALL NAIL PLATES AS NEEDED -- NEC 300.4 A 1
3. PROVIDE PROPER GROUNDING MEANS FOR ALL METAL BOXES -- NEC 250.110
4. IN ROOF J-BOX
A. NEUTRAL NOT ALLOWED TO GROUND ENCLOSURE
PROVIDE A PROPERLY SIZED EQUIPMENT GROUND -
NEC 250.24 A5
B. SELF TAP SCREW NOT ALLOWED FOR GROUNDING PROVIDE PROPER EQUIPMENT GROUND TERMINATION -- NEC 250.8
C. PROVIDE A BUSHING FOR CONDUCTOR PROTECTION WHERE NEC 300.4
THEY ENTER RACEWAY -- NEC 300.4
5. PROVIDE HALLWAY RECEPTACLE -- NEC 210.52 A
6. BATH RECEPTACLES TO BE DEDICATED -- NEC 210.11 C3