Permit: T06CM05188

Parcel: 11711076A


Addresses:

126 E ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05188

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2007 ELECTRIC - FINAL Approved PER CONVERSATION WITH RHOLLANDER. WORK DONE NEW PERMIT REQUIRED FOR ADDITIONAL WORK
12/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED ALL PAPERWORK REQUESTED
THIS CONTRACTORS SCOPE OF WORK IS COMPLETED FINAL SUBJECT TO COMPLETION OF PREVIOUS ITEMS MARKED
12/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SCREWS TO BE 4 ON CORNERS FOR FIXTURES
2. SUPPORT FLEX CONDUITS 12" OF BOXES
* 3. DIVIDERS ARE NEEDED FOR MORE THAN 300V BETWEEN DEVICES.
4. FILL UNUSED OPENINGS IN DISCONNECTS
5. CIRCUIT DIRECTORY TO BE LEGIBLE 408.4 NO ABBREVIATIONS AND LABEL ALL BREAKERS
6. VERIFY SERIES RATING OF 120V PANELS
7. PLEASE PROVIDE A LETTER FOR TORQUE VALVES AS MARKED ON EQUIPMENT
8. PLEASE PROVIDE ANY TESTING PAPERWORK FOR EQUIPMENT
9. PLANS NOT REFLECTIVE OF WORK INSTALLED. INSTALL AS PER PLANS OR HAVE SET REVISED AND RESTAMPED BY THIRD PARTY REVIEWER

OK GEAR CONNECTIONS EXCEPT AS NOTED
11/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WIRING METHOD TO BE FOR ENVIORMENTAL AIR 322
2) PLEASE VERIFY LISTING FOR PLENIUMS OF "OPTICAL FIBER ASSEMBLY
3) HAVE ELECTRICIAN HERE PRESTNT TO OPEN GEAR AND RE-ENERGIZE ALSO EQUIPMENT
4) NEED PLANS FOR LIGHTING ATTACHED TO FRAME ?
5) WHAT ARE RECEPTACLES ABOVE CEILING FOR ?
6) ATTACH FIXTURES TO GRID 410.16
7) USE OCCUPANCY SENSOR FOR CEILINGS NOT WALLS
8) BOXES AT COMBUSTIBLES TO BE FLUSH 314.20
9) PLEASE OPEN MORE TILES TO INSPECT CEILING