Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05188
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2007 | ELECTRIC - FINAL | Approved | PER CONVERSATION WITH RHOLLANDER. WORK DONE NEW PERMIT REQUIRED FOR ADDITIONAL WORK | |
| 12/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED ALL PAPERWORK REQUESTED THIS CONTRACTORS SCOPE OF WORK IS COMPLETED FINAL SUBJECT TO COMPLETION OF PREVIOUS ITEMS MARKED |
|
| 12/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SCREWS TO BE 4 ON CORNERS FOR FIXTURES 2. SUPPORT FLEX CONDUITS 12" OF BOXES * 3. DIVIDERS ARE NEEDED FOR MORE THAN 300V BETWEEN DEVICES. 4. FILL UNUSED OPENINGS IN DISCONNECTS 5. CIRCUIT DIRECTORY TO BE LEGIBLE 408.4 NO ABBREVIATIONS AND LABEL ALL BREAKERS 6. VERIFY SERIES RATING OF 120V PANELS 7. PLEASE PROVIDE A LETTER FOR TORQUE VALVES AS MARKED ON EQUIPMENT 8. PLEASE PROVIDE ANY TESTING PAPERWORK FOR EQUIPMENT 9. PLANS NOT REFLECTIVE OF WORK INSTALLED. INSTALL AS PER PLANS OR HAVE SET REVISED AND RESTAMPED BY THIRD PARTY REVIEWER OK GEAR CONNECTIONS EXCEPT AS NOTED |
|
| 11/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WIRING METHOD TO BE FOR ENVIORMENTAL AIR 322 2) PLEASE VERIFY LISTING FOR PLENIUMS OF "OPTICAL FIBER ASSEMBLY 3) HAVE ELECTRICIAN HERE PRESTNT TO OPEN GEAR AND RE-ENERGIZE ALSO EQUIPMENT 4) NEED PLANS FOR LIGHTING ATTACHED TO FRAME ? 5) WHAT ARE RECEPTACLES ABOVE CEILING FOR ? 6) ATTACH FIXTURES TO GRID 410.16 7) USE OCCUPANCY SENSOR FOR CEILINGS NOT WALLS 8) BOXES AT COMBUSTIBLES TO BE FLUSH 314.20 9) PLEASE OPEN MORE TILES TO INSPECT CEILING |