Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2007 | ELECTRIC - INTERMEDIATE | Approved | PER CONVERSATION WITH RHOLLANDER. WORK DONE NEW PERMIT REQUIRED FOR ADDITIONAL WORK | |
| 05/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RESTROOMS, BREAKROOM, UTILITY ROOM EVERYTHING NORTHEAST OF COL. LINE C5 OK WALLS |
|
| 12/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SCREWS FOR BOX MOUNTING ONLY ALLOWED IN THE BACK OF 1/4" OF BOX -- NEC 314.23 B1 2. STRAP EMT WITHIN 36" OF BOXES -- NEC 358.30 K OK TO COVER WALLS AFTER CORRECTIONS FRONT ENTRY AREAS, BATTERY ROOM, OFFICE, EQUIPMENT |
|
| 12/15/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |