Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 12/07/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEMS 1, 3, 4 NOT COMPLIED WITH ROOF NOT INSPECTED |
|
| 12/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PORCH OVERFRAME NOT BUILT PER PLAN-REQUIRES 2-2 X 10 RIDGE BEAM. RIDGE BEAM MUST BEAR ON SOMETHING OTHER THAN 1/2" OSB. PROVIDE DETAIL 2) A3 TRUSSES MISSING RAT RUNS 3) A2A AND A2B TRUSSES NOT LAYED OUT IN PROPER LOCATIONS. PROVIDE CITY OF TUCSON APPROVED REPAIR DOCUMENT 4) TRUSS ALPHA DESIGNATIONS HAVE BEEN CHANGED. HAVE TRUSS MANUFACTURER REVIEW ALL TRUSSES FOR PROPER NUMBER AND LOCATION AND PROVIDE CITY OF TUCSON APPROVED LETTER OF PROPER TRUSS LAYOUT 5) ROOF NOT INSPECTED |