Permit: T06CM05175

Parcel: 126171190


Addresses:

717 S ALVERNON WY

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
12/29/2006 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
12/28/2006 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/17/2006 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
LAVS NOT YET INSTALLED
CALL FOR 3036 AND 3090 AT SAME TIME,
LEAVE ONE CEILING TILE OPEN FOR RUN TEST INSPECTION.
10/19/2006 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SHALL SEE FINAL CONNECTION WITH RUN TEST ON 1ST FLOOR FOR THIS SINK AT HORIZONTAL TO VERTICAL SWEEP.
2. PLAN CALLS FOR COLD & HOT TO SINK, IF HOT IS REQUIRED REVISE PLAN TO SHOW INSTA-HOT HEATER.
3. SEE INSTALL OF LAVS FOR FINAL.