Permit: T06CM05174

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T06CM05174

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2007 EXCAVATION/LAYOUT REBAR & ZON Approved
03/26/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) NOTE: RFI NO PO35 REGARDING THE ELEVATOR PIT RAISED BY PLACING CONCRETE, WITH REINFORCING #4 AT 12" ON CENTER EACH WAY
03/23/2007 EXCAVATION/LAYOUT REBAR & ZON Cancelled
03/08/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
02/07/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) GRID LINE C/11 F-2 FOOTING 9'-6" X 9'-6" X 2' WITH (16) #6 H KS. EACH WAY BOTTOM
2) GRID LINE F/2-10, E/1-2, 2/E-F, 10/E-F, E/10-11 4'-0" LIFT WITH #4 AT 8" ON CENTER
02/02/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) GRID LINE C/3-9 FOOTING F-5, 3/29'-0" L FOOTING F-4, 9/29'-0"L F-4
2) GRID LINE 4.5/C-D DETAIL 1 ON SHEET S4.2
3) CORRECT INSPECTION ON 2/1/07 BY J. BURKE REGARDING COLUMN FOOTING F-3 GRID LINE A/10
02/01/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) COLUMN FOOTING (F-1) #A/9 OK TO POUR
01/31/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTING @ LINE D/3 TO D/9 FOOTING & COLUMN FOOTING (F-2)
@ LINE C/1 TO B/1; 3 @ COLUMN FOOTINGS (F-3) @ A/2; B/2
OK TO POUR
01/30/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
5 @ F-1 COLUMN FOOTINGS - LINE A/3 TO A/7 -- OK TO POUR
01/24/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
GRIDLINE A/8-9 F1 FOOTINGS WITH 8'X8'X2' (10) #6 + HKS EA. WALL BOTTOM.
GRIDLINE D/1-11 F2 FOOTING WITH 9'6" X 9'6" X 2' (16) #6 HKS EA. WAY BOTTOM
GRIDLINE 1/D-E CONTINUOUS FOOTING OR RET. WALL
01/23/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PARTIAL @ PRIOR APPROVAL FOR JIM BURGE (CLARIFICATION)
INSPECTION WAS MADE ON 1/18/07

GRIDLINE B/11-10 FOOTINGS F3 6'-6" X 6'-6" X 1'-6" WITH
(6) #6 HKS EA. WAY BOTTOM
PLUS FOOTING D-11 F2 9'-6" X 9'-6" X 2' WITH (16) #6 HKS EA. WAY BOTTOM
COLUMN FOOTING @ LINE F/9.5 TO E/11
01/22/2007 EXCAVATION/LAYOUT REBAR & ZON Cancelled
01/19/2007 EXCAVATION/LAYOUT REBAR & ZON Cancelled BY SUNDT CORP. GENERAL CONTRACTOR
01/18/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMN FOOTINGS @ LINE F/9.5 TO E/11; OK TO POUR
COLUMN FOOTINGS: D-11, A-11, A-10 -- OK TO POUR
01/17/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTINGS FOR COLUMNS (F-1) F/7, F/8, F/9
OK TO POUR
01/16/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
GRIDLINE E/1-2 F3 FOOTINGS
F/1 F3 FOOTING
F/3, 4, 5, 6 F1 FOOTINGS
CONT. FOUNDATION SAME GRIDLINES
#1 DETAIL ON SHEET S4.1
01/12/2007 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*