Permit: T06CM05145

Parcel: 140553660

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/22/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/20/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Shearwall at garage north end must have full length dbl studs installed for hold down presently blocking only
No truss drawings on site
Stopped inspection
11/16/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PRIOR INSPECTION REPORT
2) REFEE WILL APPLY
11/15/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WHY IS TRUSS A1GE BEING REPLACED WITH TRUSS AQ1G3 AND VERTICAL SUPPORT HAS BEEN REMOVED OR BROKEN
2) ITEMS 2, 6 & 3 HAVE NOT BEEN CORRECTED
11/13/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING ST2115 PER 13/DT1 IN GARAGE HEADER
2) SHEARWALL GARAGE CORNER SHOULD BE NAILED INTO DBL STUDS
3) NOTCHED BEARING WALL BOTTOM PLATE NORTH SIDE NEEDS STRAPS
4) SP4 CLIPS N/W STUD NEEDS TO BE NAILED
5) PATIO END JOISTS NEEDS A35
6) NEED DBL STUD AT REAR SHEARWALL/MASTER BEDROOM
7) NEED STRAPS SOUTH WALL BOTTOM PLATES
8) NO ACCESS TO ROOF
11/09/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) NOT COMPLETE ENOUGH TO INSPECT