Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Shearwall at garage north end must have full length dbl studs installed for hold down presently blocking only No truss drawings on site Stopped inspection |
|
| 11/16/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PRIOR INSPECTION REPORT 2) REFEE WILL APPLY |
|
| 11/15/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHY IS TRUSS A1GE BEING REPLACED WITH TRUSS AQ1G3 AND VERTICAL SUPPORT HAS BEEN REMOVED OR BROKEN 2) ITEMS 2, 6 & 3 HAVE NOT BEEN CORRECTED |
|
| 11/13/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING ST2115 PER 13/DT1 IN GARAGE HEADER 2) SHEARWALL GARAGE CORNER SHOULD BE NAILED INTO DBL STUDS 3) NOTCHED BEARING WALL BOTTOM PLATE NORTH SIDE NEEDS STRAPS 4) SP4 CLIPS N/W STUD NEEDS TO BE NAILED 5) PATIO END JOISTS NEEDS A35 6) NEED DBL STUD AT REAR SHEARWALL/MASTER BEDROOM 7) NEED STRAPS SOUTH WALL BOTTOM PLATES 8) NO ACCESS TO ROOF |
|
| 11/09/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) NOT COMPLETE ENOUGH TO INSPECT |