Permit: T06CM05144

Parcel: 140550530

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/07/2006 FRAMING Approved IVRS - Inspection :*
11/06/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO PLANS/PERMIT ON SITE
2) REPAIRS NOT MADE
11/03/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RED HEAD ANCHOR BOLTS LOOSE
2) PLAN CALLS FOR KITCHEN DWV TO VENT TO ROOF
3) KITCHEN SHEAR MISSING ANCHOR BOLT
4) MASTER SHOWER NOT PROPERLY VENTED MUST VENT ABOVE CENTER LINE OF DRAIN
5) DUCT WORK NOT ?
6) 14" DUCT RESTRICTED
7) UPSTAIRS HALL BATH TOILET AND TUB NOT PROPERLY VENTED