Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CONTROL CABINETS HAVE BEEN FIELD LISTED BY UL |
|
| 12/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. APPROVAL OF CONTROL CABINETS SUBJECT TO OFFICE APPROVAL. 2. HA PNL MAINS FOR H1, H2, H3, H4 OK WIRING OF CABINETS & CONVEYOR MOTORS OK 3. ROBOT CONTROLLER NOR ROBOT -- NO INDICATION OF ANY LISTING ON EITHER. |
|