Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1) SERVICE INSPECTION-SEE T06CM05079 |
|
| 03/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK GROUNDING, BLD STEEL, FUSES, R.PINS, FOR SERVICE 2. NEED APPROVAL FOR OVERHEAD WAIVER FOR SERVICE. |
|
| 03/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GROUNDS FOR BOND BUSHINGS ON UTILITY SIDE TO BE SIZED PER 250.66 2) HUBS NOT LISTED FOR SERVICE GROUNDING, AT RISER CONDUITS 3) INSTALL FUSES AND R-PINS 4) OVERHEAD WAIVER REQUIRED FOR OVERHEAD SERVICE |
|
| 03/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OFFICE WALLS EXCEPT PONY WALL NOT DONE YET OK RESTROOM WALLS NO EXH. FANS YET |
|
| 02/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CHECK TO MAKE SURE SPACE #'S ARE PER PLAN |