Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM05114
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/22/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) INSTALL MID SPAN BLOCKS FOR SHEAR 2) ADD TWO WIND BRACES 3) NEED TRUSS DRAWINGS |
|
| 11/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) MISSING WIND BRACING THRU-OUT 2) 3 PT BEARING TRUSSES TO BE BLOCKED 3) NEED PLAN TO CHECK H.D'S 4) DO SHEAR PANELS GET NAILED TO ROOF 5) NEED TRUSS DRAWINGS |
|
| 11/14/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO LADDER 2) 2 LTT20B H.D. LIVING ROOM AND MASTER BEDROOM SHEARWALLS 3) H.D.'S GARAGE WALL NEES TO BE ANCHORED 4) LTT20B H.D. GARAGE WALL PER 3 CAN GARAGE OPTIONAL 5) MISSING KING STUD PER 13/DT1 AT SMALL GARAGE DOOR OPENING 7) NEED H2.5 CLIPS OF EQUIPMENT AT STUD, INTERIOR SHEAR TRANSFER WALL MASTER BEDROOM 8) STRAP HEADER ON PATIO SHEARWALL PER 17/DT1 |