Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05111
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/09/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FLEX CONNECTOR ON TYPE 1 EXHAUST MUST COMPLY WITH SECTION 506.3.2.4 2003 I.M.C AIR BALANCE REPORT OK |
|
05/01/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO FILE FOR TEMP C OF O |
|
04/30/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. EXHAUST CLEANOUT ON ROOF MUST USE WING NUTS TO REMOVE. 2. PAINT ALL BLACK IRON EXPOSED ON ROOF. 3. PROVIDE THE LISTING FOR FLEX CONNECTOR USED FOR TYPE 1 APPLICATION. 4. PROVIDE A GREASE CUP UNDER EF-2 5. SMOKE DETECTORS NOT SHUTTING DOWN FANS, NO VISIBLE ALARM. 6. PROVIDE AIR BALANCE REPORT |