Date Description Inspector Results Comments
05/16/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/09/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FLEX CONNECTOR ON TYPE 1 EXHAUST MUST COMPLY WITH SECTION 506.3.2.4 2003 I.M.C
AIR BALANCE REPORT OK
05/01/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK TO FILE FOR TEMP C OF O
04/30/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. EXHAUST CLEANOUT ON ROOF MUST USE WING NUTS TO REMOVE.
2. PAINT ALL BLACK IRON EXPOSED ON ROOF.
3. PROVIDE THE LISTING FOR FLEX CONNECTOR USED FOR TYPE 1 APPLICATION.
4. PROVIDE A GREASE CUP UNDER EF-2
5. SMOKE DETECTORS NOT SHUTTING DOWN FANS, NO VISIBLE ALARM.
6. PROVIDE AIR BALANCE REPORT