Permit: T06CM05111

Parcel: 136261270

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
04/20/2007 MECHANICAL - HOODS Approved IVRS - Inspection :*
FIRE WRAP OK
INSULATE CONDENSATE.
LEAVE OUT TILES AROUND CONDENSATE DRAINS AND DUCT SMOKE DETECTORS
04/02/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCTS
OK TO FIRE WRAP
03/21/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK TO INSULATE CONDENSATE DRAINS WITH 3/4" ARMAFLEX OK TO INSULATE DUCT WORK WITH MIN. R5 (2") INSULATION