Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05111
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EMERGENCY EGRESS LIGHTING NOT WORKING 2. RECALL FOR INSPECTION OF DRIVE THRU SIGNS WHEN INSTALLED 3. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED OK FOR TEMP C OF O |
|
04/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY PER NEC 408.4 2. INSTALL SERVICE DISCONNECTS ON FAN COIL UNITS INSIDE WALK IN COOLERS 3. EMERGENCY LIGHTS NOT WORKING 4. MC CABLE TO FIRE ALARM PANEL TO BE CONNECTED WITH CONNECTOR. 5. INSTALL LOCK NUTS ON EMT CONNECTORS AT FIRE ALARM PANEL. 6. RECEPTACLE IN TRAINING ROOM HAS NO POWER 7. LABEL DISCONNECT SWITCHES IN WTR HTR CLOSET 8. ONE WIRE PER LUG AT DISCONNECTS ON ROOF 9. CANNOT CONNECT GROUNDS WITH SHEETMETAL SCREWS 10. ONE DISCONNECT ON ROOF NOT GROUNDED 11. INSTALL MISSING COVERS ON OUTSIDE LIGHTS 12. DRIVE THRU SIGNS NOT INSTALLED AT THIS TIME |