Permit: T06CM05111

Parcel: 136261270

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05111

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EMERGENCY EGRESS LIGHTING NOT WORKING
2. RECALL FOR INSPECTION OF DRIVE THRU SIGNS WHEN INSTALLED
3. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED

OK FOR TEMP C OF O
04/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORY PER NEC 408.4
2. INSTALL SERVICE DISCONNECTS ON FAN COIL UNITS INSIDE WALK IN COOLERS
3. EMERGENCY LIGHTS NOT WORKING
4. MC CABLE TO FIRE ALARM PANEL TO BE CONNECTED WITH CONNECTOR.
5. INSTALL LOCK NUTS ON EMT CONNECTORS AT FIRE ALARM PANEL.
6. RECEPTACLE IN TRAINING ROOM HAS NO POWER
7. LABEL DISCONNECT SWITCHES IN WTR HTR CLOSET
8. ONE WIRE PER LUG AT DISCONNECTS ON ROOF
9. CANNOT CONNECT GROUNDS WITH SHEETMETAL SCREWS
10. ONE DISCONNECT ON ROOF NOT GROUNDED
11. INSTALL MISSING COVERS ON OUTSIDE LIGHTS
12. DRIVE THRU SIGNS NOT INSTALLED AT THIS TIME