Permit: T06CM05111

Parcel: 136261270

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05111

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER OF TORQUE
04/17/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROTECT #4 & LARGER CONDUCTORS PER
NEC 352.46 AND 300.4
2. MORE THAN 10' OF COPPER WTR PIPE IN GROUND. CONSIDERED GROUNDING ELECTRODE SIZE CONDUCTOR PER NEC 250.66, 250.52
04/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TRIM
03/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK ROUGH CONDUIT, EXCEPT WALK IN COOLER
2. CALL WHEN WIRE PULLED IN CONDUIT PRIOR TO TRIM