Permit: T06CM05110

Parcel: 106030470

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05110

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2007 ELECTRIC - FINAL Approved
04/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND ALL SWITCHES -- NEC 404.9B
2. PROVIDE ARC FAULT PROTECTION FOR BEDROOM SMOKE DETECTOR - NEC 210.12B
3. INSTALL RANGE ANTI-TIP DEVICE - NEC 110.3B
4. INSTALL HOT WATER HEATER J-BOX COVER PLATE
5. HAVE REVERSE POLARITY ON KITCHEN RECEPTACLES
6. PROVIDE CONNECTOR FOR ROMEX INTO HOOD - NEC 314.17
7. INSTALL PROPER SIZE BULBS IN ALL FIXTURES AND HOOD
8. HAVE LOOSE RECEPTACLES THROUGHOUT - NEC 406.4
9. CLOSET LIGHT FIXTURE TO HAVE TOTALLY ENCLOSED BULB
NEC 410.8 B1
10. TIGHTEN PANEL SCREWS

THERE WILL BE A FEE IF ALL NOT CORRECT NEXT INSPECTION
11. NEED CONNECTOR FOR RANGE CORD.
03/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) GROUND BAR ON SIDE OF PANEL NEEDS TO BE MOUNTED TO ENCLOSURE BY A TAPPED HOLES AND MACHINE SCREWS NOT SHEET METAL OR WOOD SCREWS-NEC 250.8
WILL PAY REFEE IF NOT CORRECT NEXT INSPECTION
03/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINAL WILL BE INSPECTED AFTER POWER IS APPROVED
FOR POWER TO BE APPROVED
1. NEED BUSHING FOR FEEDER WHERE IT ENTERS PANEL
NEC 300.4F
2. RE-IDENTIFY GROUND AND NEUTRAL FOR FEEDER
3. SELF TAP SCREWS NOT ALLOWED FOR GROUND BAR
NEC 250.8
4. USE PROPER GROUND BAR THAT PROVIDES FOR PROPER TERMINATION FOR CONDUCTOR SIZES.
5. NEED FRESH OXIDATION INHIBITOR FOR ALL ALUMINUM TERMINATIONS AND TIGHTEN ALL TERMINATIONS IN PANEL.
6. RANGE NEUTRAL TO BE CONNECTED TO NEUTRAL BAR - NOT GROUND BAR.