Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05106
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2007 | FRAMING | Approved | IVRS - Inspection :* | |
06/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH NAILING OFF FHA STRAP MINIMUM 8-16D NAILS BOTH SIDES OF OVERNOTCHED PLATE 2) ANCHOR BOLTS STILL NEEDED FOR BOTH MAIN FLOOR BATHROOM SHEARWALLS PER PLAN 3) FINISH STUCCO MESH AROUND ELECTRICIAN PANEL 4) SEAL VENT TERMINATIONS ON NORTH WALL OF HOUSE 5) FINISH NAILING OFF FHA STRAP ON MAIN FLOOR 2 X 6 SHEARWALL IN BATH 6) MOVE WIRES AWAY FROM GUSSETS OF TRUSSES |
|
06/21/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) 2 ANCHOR BOLTS MINIMUM FOR SOLE PLATE SOUTH OF OVERHEAD DOOR AND NORTH 2) MAX 12" FROM ? OF SOLE PLATE FOR ANCHOR BOLT SOUTH WALL IN GARAGE 3) ANCHOR BOLTS BOTH SOLE PLATES MAIN FLOOR BATH SHEARWALLS 4) WIRES OUT OF PONY WALL OF STAIRS |