Permit: T06CM05106

Parcel: 141350100

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM05106

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2007 FRAMING Approved IVRS - Inspection :*
06/25/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH NAILING OFF FHA STRAP MINIMUM 8-16D NAILS BOTH SIDES OF OVERNOTCHED PLATE
2) ANCHOR BOLTS STILL NEEDED FOR BOTH MAIN FLOOR BATHROOM SHEARWALLS PER PLAN
3) FINISH STUCCO MESH AROUND ELECTRICIAN PANEL
4) SEAL VENT TERMINATIONS ON NORTH WALL OF HOUSE
5) FINISH NAILING OFF FHA STRAP ON MAIN FLOOR 2 X 6 SHEARWALL IN BATH
6) MOVE WIRES AWAY FROM GUSSETS OF TRUSSES
06/21/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) 2 ANCHOR BOLTS MINIMUM FOR SOLE PLATE SOUTH OF OVERHEAD DOOR AND NORTH
2) MAX 12" FROM ? OF SOLE PLATE FOR ANCHOR BOLT SOUTH WALL IN GARAGE
3) ANCHOR BOLTS BOTH SOLE PLATES MAIN FLOOR BATH SHEARWALLS
4) WIRES OUT OF PONY WALL OF STAIRS