Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SECURE EXTENDER RING TO FIXTURES - BATHS PARTIAL INSPECTION - FINISH PREVIOUS ITEMS |
|
| 01/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK MECHANICAL ROOM MRI OK ROOF OK POLES & BOLLARDS OK EXAM ROOM OK OFFICES |
|
| 01/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN CLEARANCES OF INSULATION AT CANS 2. SUPPORT VDV CABLING AS PER 725.6, 800.6 AND 300.11 3. VERIFY MRI - ALSO, LISTING CK OUTSIDE POLES, ROOF AND SERVICE NEXT TIME |
|
| 01/24/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MISSING FIXTURES BATHROOMS 2. PANEL DIRECTORY AS PER 408.4 - NO ABBREVIATIONS WHERE DO THEY GO TO? 3. GFI NOT WORKING 4. FINISH ELECTRIC |