Permit: T06CM05102

Parcel: 10824011A


Addresses:

2450 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM05102

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
12/03/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SERVICE AND DISTRIBUTION

1. NEED TO POST BOND FOR POWER
2. NEED PERFORMANCE TEST FOR SERVICE - NEC 230.95
3. INSTALL SECONDARY CONDUCTORS
4. PROVIDE LETTER OF TORQUE FOR SERVICE
5. HVAC DUCT NOT ALLOWED ABOVE SERVICE - NEC 110.26 F
6. PULL CHILLER FEEDER
7. MAKE SURE ALL FEEDER EQUIPMENT GROUNDS ARE INSTALLED

PARTIAL INSPECTION

8. NO OPEN WIRING FOR POWER (FINISH TRIM)
9. INSTALL PANIC HARDWARE FOR SERVICE ROOM DOOR AND ILLUMINATION IN ROOM - NEC 110