Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM05102
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
12/03/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE AND DISTRIBUTION 1. NEED TO POST BOND FOR POWER 2. NEED PERFORMANCE TEST FOR SERVICE - NEC 230.95 3. INSTALL SECONDARY CONDUCTORS 4. PROVIDE LETTER OF TORQUE FOR SERVICE 5. HVAC DUCT NOT ALLOWED ABOVE SERVICE - NEC 110.26 F 6. PULL CHILLER FEEDER 7. MAKE SURE ALL FEEDER EQUIPMENT GROUNDS ARE INSTALLED PARTIAL INSPECTION 8. NO OPEN WIRING FOR POWER (FINISH TRIM) 9. INSTALL PANIC HARDWARE FOR SERVICE ROOM DOOR AND ILLUMINATION IN ROOM - NEC 110 |