Permit: T06CM05102

Parcel: 10824011A


Addresses:

2450 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/25/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/24/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/16/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK COVER ROOM 501 & 502
10/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK COVER SECRETARIAL AREA 401, 402
OK HARD LID SOFFITS NORTH TO SOUTH ENTRY CORRIDORS
OK HARD LID SOFFIT AREA 604
10/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER CEILING (HARD LID) IN BOARD ROOM
(MAKE J-BOX @ PROJECTOR ACCESSIBLE)
OK HARD LID SOUTH STORAGE ROOM
OK SOFFITS B A5 TO WATERFALL
10/08/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK X-RAY ROOM COVER (WALL) AND OFFICES DIRECTLY
WEST OF X-RAY
09/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SOFFITS FROM SOUTH END TO COLUMN LINE B/A5
2. OK WALLS DRESSING ROOMS 1801, 1802, 1803, 1805, 1804
3. OK WALLS RMS 3305, 3307 AND WEST WALL OF RM 604 & DRESSING ROOMS
4. OK SHEAR WALL FROM COLUMN LINE A/A5 NORTH
09/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OUTSIDE WALLS RMS 604, 1805, 1806, 4205, 1402, 1302, 1301, 1401, 1703, 3206, 3201
09/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER EXTERIOR SOFFITS AS NEEDED WHEN LIGHTING COMPLETED
09/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 101-105, 118-122, 301-305, 330-326, 4701, 201, 212
09/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED PROPER CLEARANCES @ GEAR & PLAN SHOWS
2ND EXIT
OK WALL COVER INTERIOR FROM SOUTH TO C (PLUS) EAST/WEST CORRIDOR

NOTE: DO NOT DRYWALL/INSULATE BEFORE APPROVAL IN FUTURE

RAYCO BOXES APPROVED OVER 250V FOR CONCENTRICS/ECENTRICS